INDUSTRIAL ENVIRONMENT
Master Industrial is suitable for the most demanding installation environments where there is vibration, mechanical stress, dust and, in general, where the operating conditions are unfavourable to products created for the standard UPS market.
HIGH ICC
The high short-circuit current (ICC = 3xIn) makes it suitable for loads that require high current peaks during start-up or normal operation.
DC VOLTAGE 220 V
The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 cells), the standard industrial value.
REDUNDANT VENTILATION
Redundant ventilation at 100% load is standard, guaranteeing normal load operation with half the fans running; in addition, each fan is monitored and an alarm signal is given in the event of a fault. The features of the Easy Source input, Battery Care System, flexibility and communication capabilities are the same as those of the classic Master MPS range.